| RaneNote
The grounding and shielding of audio devices
By Steve Macatee
|


1 2
3

|
Solutions for Mixed Balanced and Unbalanced Systems
It is obvious from the vast quantity of literature that for fully
balanced operation, the shield should connect to chassis ground
at the point of entry. This is also true for unbalanced operation
when a third shield conductor is available; connect the shield to
chassis ground at the point of entry. However, this is only valid
when 2-conductor shielded cable is used.
Shielded 2-Conductor Connectivity
Figure 5 shows recommended wiring for all combinations of balanced
and unbalanced I/O interconnections when 2-conductor shielded cable
is used. Figure 5 also includes the two most common manufacturer
shield-grounding schemes; signal-grounding the shield and chassis-grounding
the shield. Identifying these schemes for every unit in a system
is essential to debug system hum and buzz. This is no simple task
since chassis and signal grounds are connected together. The goal
is to find out if the manufacturer connected them together is such
a way that shield currents do not affect the audio signal. The dashed
lines in Figure 5 represents the units' chassis boundary. Connections
between dashed lines are functions of the cable. Connections outside
these lines are the manufacturer's choosing, whether conscious or
unconscious.
Figure 5 is arranged such that the top and left most figure (5a)
is the theoretical "best" way to connect equipment with
optimal results. The "best" way being, everything completely
balanced with all shields (pin 1s) connected to chassis ground at
the point of entry. As one moves down or to the right, degradation
in performance is expected. Whether a system operates acceptably
or obeys these theoretical predictions is too system-specific to
predict accurately. However, one must start somewhere.
The quality and configuration of the input and output circuits are
omitted from Figure 5 and the ensuing discussion, to focus on cable
wiring and the internal wiring of the units. The I/O circuitry is
assumed ideal.
| 
Figure 5: Interconnectivity using
shielded 2-conductor cable only. Asterisks denote usability
with off-the-shelf cable.
|
Fully Balanced
Fully balanced systems (left column in Figure 5) provide the best
performance when both ends of the shield connect to units with chassis-grounded
shields (Figure 5a). When units with signal-grounded shields are
encountered, disconnect the shield at the signal-grounded end (Figures
5b & 5c). This keeps the induced shield currents out of the
audio signal ground. If both units involved have signal-grounded
shields, you have entered the twilight zone (Figure 5d). This is
perhaps the most common scheme. Most disconnect one end of the shield,
specifically which end is disconnected creates strong political
debates and is left for the individual user to decide [6]. Never
disconnect both ends of a shield.
Unbalanced Output Driving Balanced Input
The second column in Figure 5 shows unbalanced outputs driving balanced
inputs. Again, only shielded 2-conductor cable is used. The best
case here has both ends of the shield connected to units whose shield
is chassis-grounded (Figure 5e). Some may argue that the induced
noise on the signal conductors may be injected into the "sending"
unit through the unbalanced output stage. This is a function of
the system and output circuit, and is quite likely. Disconnecting
the shield at the unbalanced output might reduce this problem.
When units with signal-grounded shields are encountered, disconnect
the shield at the signal-grounded end (Figures 5f & 5g). This
keeps the noisy shield currents out of the audio signal ground.
If both units involved have signal-grounded shields, you've entered
the twilight zone again (Figure 5h). Support your one-end-only political
party (Figure 5l).
Balanced Output Driving Unbalanced Input
The third column in Figure 5 is the most troublesome, balanced outputs
driving unbalanced inputs. Since the input stage is not balanced,
induced noise on the signal conductors is not rejected. If you must
use an unbalanced input, use as short an input cable as possible.
This reduces the induced noise. There's a reason it's hard to find
and buy unbalanced RCA cables longer than 12 feet. Figure 5i shows
both ends of the cable shield connected to units with chassis-grounded
shields. If the units are far apart, the chance of the shield currents
inducing noise on the signal conductors is greater. Keeping this
cable very short reduces the shield current and therefore reduces
the noise that is not rejected by the unbalanced input stage. Most
systems may require disconnecting one end of the shield for the
Figure 5i case. Even a small current in the shield may prove too
much for an unbalanced input stage. Again, support your favorite
one-end-only political position.
Disconnect the shield at units with signal-grounded shields (Figures
5j & 5k). If both ends have signal-grounded shields, run for
your favorite one-end-only political party. (Figure 5l).
This scheme connects the balanced output's negative output to signal
ground, rather than a high impedance input. Many balanced output
circuits will attempt to drive this signal ground, causing great
distortion and potentially damaging the output stage. Other balanced
output stages are termed "floating" balanced. (Analog
Devices SSM-2142 Balanced Line Driver chip is one example.) Also
called a cross-coupled output, these circuits mimic the performance
of fully balanced transformer solutions and are designed so the
negative output can short to signal ground. If you find or use this
scheme, be sure that the balanced output stage can properly handle
signal ground on its negative output.
Full Unbalanced
Fully unbalanced systems do not provide a 3-conductor connector
to enable proper use of a shield. In the unlikely event you run
across one, use the wiring in the fourth column (Figure 5m-p). Again
keeping cable lengths short will reduce noise problems, with or
without a shield.
Most home audio systems are fully unbalanced. Millions of these
systems work virtually hum and buzz-free every day, due to their
small nature, short cable runs and 2-conductor AC line cords. The
headaches begin when one tries to add a balanced unit to such a
system. In unbalanced home audio products neither of the line cord's
conductors connects to the chassis, since plugging older, non-polarized
AC plugs into an improperly wired outlet would place the "hot"
wire on the unit's chassis. Lack of the third pin on the line cord
prevents ground loops in home systems since a second path to ground,
or between units, is unavailable. Professional audio equipment generally
comes equipped with a 3-wire line cord. The third wire (green wire)
is required to connect to the chassis. This provides the second
ground path (loop) from one unit to the next.
Connector Choice
Connector type was purposely left out of Figure 5 and the above
discussion since connector choice adds another layer of complexity
to interconnection systems. The most troublesome culprit is the
1/4" connector. Mono 1/4" connectors are used on most
musical instruments and in phone systems. Stereo 1⁄4"
connectors are used for headphones, balanced interconnection, effect
and insert send/return loops, relay switch closure points, and an
extravagant collection of other miscellaneous connections. Murphy's
Law tells us, if you provide such a diverse selection of 1/4"
interconnection options, they will be hooked up improperly. The
audio industry's problem is that many of these options are completely
incompatible. A properly wired mono 1/4" connector has signal
ground on the sleeve, a properly wired balanced 1/4" connector
has chassis ground on the sleeve. Interconnecting this combination
should not be achievable -- much like trying to connect 120 VAC
to an RCA jack (see Figure 6). The 1/4" connectors low cost,
high availability, and small size all contribute to its widespread
and varied use. Undoubtedly the numerous interconnection uses of
such a popular connector arose for these reasons.
| 
Figure 6: Difficult-to-find connector
type.
|
Sadly, the possibility of including connector type in a recommended
practices document is slim. The duplicate connectors on many audio
components contributes to higher costs and wastes millions of dollars
worth of connectors that are never used. Some manufacturers are
attempting to eliminate the 1/4" connector to avoid the confusion
and problems when 1/4" jacks are used. This is a step in the
right direction, though the high density allowed by these connectors
requires less valuable rear-panel real estate. Most marketing departments
prefer thirty connectors per inch, making the currently available
3-pin (XLR) alternative markedly unpopular. What is needed is a
3-pin connector solution that requires less space than the traditional
XLR connector. A locking, stackable 3-pin mini-DIN comes to mind.
Terminal block and Euroblock connector types are used when separate
cable-end connectors are unnecessary or impractical. These connection
solutions provide the user with the most wiring options when both
signal and chassis ground terminals are available. This allows the
user to decide which wiring practice to incorporate. This is the
most desirable solution, though most studio equipment does not call
for these connector types.
"Hidden" Balanced I/O Solution
An interesting solution for mono interconnection incorporates unshielded
balanced stages, much like most telephone systems. Figure 7 shows
this configuration. This allows off-the-shelf mono cables to be
used to connect unbalanced or unshielded-balanced I/Os to a system.
Though not as ideal as a shielded balanced interconnection, systems
with mono connectors, like home theatre systems, benefit from this
configuration. Keeping cable lengths short is essential and not
difficult in a home environment.
| 
Figure 7: "Hidden" Balanced Interconnection.
|
One advantage of such a system, besides making it impossible,
on fully balanced systems, to get signal ground on an external cable,
is that it provides an easy upgrade path to balanced signal connections.
The manufacturer need only change the connector to a 3-pin version.
Also crucial for this solution is the need to have either cross-coupled
output stages or an output that does not mind a grounded negative
output, since the negative output may connect to signal ground.
A slight disadvantage lies with the common use of non-twisted pair
cables in off-the-shelf mono cables. Using twisted cable with this
unshielded balanced scheme greatly improves the achievable performance.
The Muncy Solution
Neil Muncy is an electroacoustic consultant and veteran of years
of successful system design. His long standing solution to these
issues provides real-world proof of the guaranteed performance achievable
with fully balanced systems wired per the Audio Engineering Society
recommendation. Mr. Muncy implements what I call the Muncy solution
and alters every piece of gear so it has balanced inputs and outputs
with both ends of the shield connected to chassis ground at the
point of entry. Decades of this practice, and the early research
and discipline to understand the basic physics required to implement
it properly, have given Mr. Muncy the drive to tirelessly tour the
country dispersing his findings. Mr. Muncy's seminars educate those
who are ignorant of the "right" way to wire balanced equipment,
and show the advantages gained when every piece of gear in the system
is wired accordingly.
Current Manufacturer Solutions
Let's examine manufacturer's choices regarding signal-grounding
or chassis-grounding balanced cable shields. The problems of signal-grounding
balanced shields have already been covered. Users choose to live
with hum & buzz, alter off-the-shelf cables by disconnecting
one end of the shield or, even in fully balanced systems, use isolation
transformers. All are senseless alternatives for inconsistent manufacturing
methods. Their advantages and disadvantages are outlined in Tables
1 and 2.
For the manufacturer, several shield connectivity choices are
available.
1. Keep or change shield connections to chassis ground.
Manufacturers who chassis-grounded balanced shields originally must
still recommend isolation transformers, cable altering and the technical
support that go with these hum and buzz solutions. This is unfortunately
necessary, since not all balanced equipment has chassis-grounded
shields. Ideally, if all balanced equipment were suddenly and miraculously
chassis grounded on both ends at the point of entry, off-the-shelf
cables could be used in every system, leaving only the I/O circuitry
to dictate system performance.
2. Change shield connections to signal ground.
Though this would be a step backward, it is still a choice. Most
equipment is connected this way and most users have found their
own costly "add-on" interconnection solutions.
3. Offer the shield connection choice to the user.
Provide both options. Two independent screw terminals (one signal,
one chassis), a switch or a jumper option permit the user to wire
as they please. More on this later.
Manufacturer Solutions for Efficiently and Effectively Connecting
Balanced Shields to Chassis
Printed Circuit Board Mounted Jacks
The printed circuit mounted jack provides manufacturers with the
most cost-effective solution for transferring cable signals to a
printed circuit board. On the board, most manufacturers connect
the balanced shield conductor (to signal ground) with a board trace.
For optimum balanced performance connect the shield to chassis ground
at the point of entry. This means that the shield conductor, to
avoid spraying any induced RF energy into the box, never passes
the chassis' outer plane. This is not a simple task. Currently no
printed circuit mounted 3-conductor connectors provide this optimum
solution.
Terminal Strips
When both signal and chassis ground terminals are provided on terminal
block or Euroblock connector types, the user decides which wiring
practice to incorporate. This is a desirable solution, though a
lot of equipment does not call for these connector types. Providing
a Pem nut, screw and toothed washer near the cable terminals, instead
of an additional chassis-grounded screw terminal, prevents the shield
conductor from entering the enclosure -- supplying the ultimate
interconnection solution. (This is why Rane terminal strips and
Euroblock inputs and outputs have a PEM nut, screw and tooth washer
above the shield connection.) Users select their preferred wiring
practice, and the shield can not spray RF into the enclosure. Maintaining
the shield around the signal conductors all the way to the I/O terminals
is important. Keeping the Pem screw near the terminals is therefore
essential.
Panel Mount Jacks with Wires
Panel mount jacks require the manufacturer to connect a wire from
a terminal pin to the printed circuit board or chassis. This is
a good solution for chassis-grounding a shield, though this allows
the shield to enter the enclosure. Keep the wire short, the gauge
large, and the path to chassis away from sensitive circuits. "Wire"
is a four letter word to many manufacturers, and some consider them
too costly due to their labor intensive nature. Achieving consistent
results with hand-wired connections is difficult, making the PC
mounted jack solution more desirable.
L-Bracket or Standoff Solution
A circuit board trace run to a nearby chassis-grounded point is
another option. Use of an L-bracket, standoff or similar mechanical
connection to the chassis provides mechanical stability, but also
consumes valuable rear panel and/or PC board real estate at the
same time. Important here is avoiding long traces and keeping the
trace away from sensitive areas since it acts as a noise source
when shield currents are large or noisy.
Jumper Options
Not as "friendly" as the screw terminal solution, an internal
jumper option provides user configuration of internal shield connection
points. This allows the use of XLR or 1/4" connectors yet still
gives the user control of shield wiring practices. Providing a separate,
external switch for this function is not cost effective. Two issues
arise with this solution. The first is that there is no external
visual indication showing shield connection point. The second issue
to address is which position to ship the jumpers in.
The first problem is nothing new. Most manufacturers do not specify
where their shields are connected. The unit's manual or schematic,
if available, may indicate what ground connects to the shield. The
schematic symbols used for grounds are not standardized, though
there is an Audio Engineering Society standards group addressing
drafting symbols to solve the dangling triangle mystery. Proper
schematics indicate which symbols represent signal and chassis grounds.
The second issue's answer is clear -- chassis-grounding the balanced
shield is the "best" default option, though offering the
choice supplies an elegant solution for parties on both sides of
the fence. For fully balanced systems, defaulting the shield jumper
to chassis provides the best solution, but only when all interconnected
units have chassis-grounded shields. Other units with signal-grounded
shields short-circuit the shield currents to signal ground when
connected, causing potentially nasty modulation of the signal ground.
This makes the other guy appear the culprit, but does nothing to
solve the problem. Clearly users must be able to determine manufacturer
shield wiring practices. Additionally, to support both "one-end-only"
shield connection parties, separate input and output jumpers must
be provided (see Figure 8).
| 
Figure 8: User-Selectable Shield Connections.
|
Neutrik Solution
Neutrik AG, Liechtenstein, offers snap-in, printed circuit mount
jacks with metal brackets which pierce the inside of the chassis
when external mounting screws are installed. This chassis-pierced
bracket also has a separate pin available through the printed circuit
board. The sharp piercing tab provides the electrical connection
between the chassis housing and printed circuit board. This solves
the problems of the labor intensive wire and the need to connect
to a chassis point, providing the best solution for manufacturers
and users. [Neutrik's popular "combo" receptacles -- combined
female XLR & female 1/4" connectors -- provide this piercing
tab feature.] Unfortunately, depending on the available height in
a given unit, these jacks have trouble fitting in a single rack
space unit due to their slightly larger height. Hopefully other
jacks with this built-in feature will become available, providing
manufacturers with a cost effective solution to this grounding problem.
Other Suggestions
Many years ago RCA developed their own guidelines for rear panel
I/O practices. Some manufacturers and users practice their own methods
of left to right interconnection customs. AC and speaker level I/O
on one side, microphone and lower level signals on the other side.
This permits easier rack wiring and decreases crosstalk between
cable runs in the rack and along cable paths. While the recommended
practices document may not dictate product design at such a basic
level, this type of thinking benefits everyone. With multi-manufacturer
standardized network-controlled products popping up everywhere,
now is the time to address these basic features. Users with "standardized"
interconnection systems, designed with the user in mind by informed
engineers, will spend less time debugging and installing systems.
This allows more installations per day, generates better, quieter
systems and provides more business with smiling users and manufacturers.
Fiber is the Future
Digital fiber optic interconnection solves all the above problems
of electrical interconnection systems, though one must face a new
set of problems. However, when one adds up the debugging costs of
eliminating hum from electrical systems, fiber may not seem as expensive.
Conclusion
Balanced and unbalanced interconnection are two very different beings.
The incompatibility between these two configurations, whether using
analog or digital signals, must be considered when designing, specifying,
installing or upgrading equipment and systems. Literature on the
subject of grounding and shielding audio devices dictates chassis-grounding
balanced shields. Most manufacturers, however, signal ground their
balanced shields. Speculation about how and why this practice materialized
was explored. The Audio Engineering Society is developing a recommended
practices document which also condones chassis-grounding balanced
shields, among other things. It was shown that the manufacturer
choice of signal-grounding or chassis-grounding balanced shields
does not affect the cable re-wiring and other technical support
solutions normally recommended when interconnection of balanced
and unbalanced equipment is needed. Therefore manufacturers need
not hesitate in addressing their "pin 1 problems," and
should provide users with the real benefits of balanced interconnection
by providing chassis ground on balanced shields. Efficient and effective
ways of doing this were also discussed.
Also covered was the importance of reducing signal ground voltages
between interconnected units by carefully and properly connecting
chassis ground to signal ground, in one place, in each unit. Vitally
important is the manner in which one connects these two grounds
together. The same care must be taken when connecting I/O cable
shields to the chassis ground. One must avoid common impedance coupling
in the shield-to-chassis trace to ensure optimum performance from
balanced interconnection.
The goal of the Audio Engineering Society in recommending these
balanced interconnection solutions is to reduce or eliminate the
need for interconnection work-arounds through education and information
sharing. This is the mission statement of the Audio Engineering
Society in the first place. Systems installed with chassis-grounded
balanced shields on all units, with well-twisted interconnection
cables operate hum and buzz-free, leaving only the input and output
circuit topology specifications to dictate system performance.
The Audio Engineering Society recommendation's purpose is not to
create another "pin 2 is hot" war. In reality, users and
installers have found acceptable solutions for "the pin 1 problem"
of signal-grounded balanced shields and are unlikely, nor will they
be able, to suddenly change over to not using alternatives. Manufacturers
specify I/O connector type on data sheets, similarly, we should
specify shield connection practices in equipment specifications,
on the chassis, or at least in the manual, thus providing users
with required information for proper system configuration.
References
1. Ott, Henry W., Noise Reduction Techniques in Electronic Systems
(John Wiley and Sons, Inc., NY, 1976).
2. Morrison, Ralph, Grounding and Shielding Techniques in Instrumentation
(John Wiley and Sons, Inc., NY, 1967).
3. Morrison, Ralph, Noise and Other Interfering Signals (John Wiley
and Sons, Inc., NY, 1992).
4. Giddings, Philip, Audio System Design and Installation (Howard
W. Sams, 1990).
5. Jung, Walt and Garcia, Adolfo, Op Amps in Line-Driver and Receiver
Circuits, Part 2, (Analog Dialogue Vol. 27, No. 1, 1993).
6. Whitlock, Bill, "System Problems and Equipment Manufacturers"
(Systems Contractor News, September 1997).
7. Perkins, Cal, Measurement Techniques for Debugging Electronic
Systems and Their Interconnection, (Proceedings of the 11th International
AES Conference, Portland, OR, May, 1992).
8. Sound System Interconnection, (Rane Corporation, Mukilteo,
WA, 1985).
9. Metzler, Bob, Audio Measurement Handbook, (Audio Precision, Portland,
OR, 1993).
A version of this RaneNote was published in the Journal of the Audio
Engineering Society, Vol. 43, No. 6, June, 1995.
|