The Benefits of Series Mode Surge Suppression
Neil A. Muncy, Neil Muncy Associates
Markham, ON, Canada
|

1 2

|
Fundamental differences between Shunt Mode and Series Mode surge suppressors are examined. It is shown that the indiscriminate use of Shunt Mode surge suppressors in applications such as sound systems and computer networks can cause more problems than are supposedly eliminated by the use of such devices. Suggestions for optimal deployment of both types of devices are presented.
INTRODUCTION
Multiple sources of transient electrical noise (surges) including motors, HVAC equipment, photocopiers, power tools, etc, are present in all modern buildings. Surge energy conveyed by building power systems may also result from external sources such as nearby lightning strikes. To minimize the likelihood of injuries to personnel and damage to equipment due to electrical surges and accidental fault conditions, in North America the National Electrical Code (NEC) specifies that all exposed electrical equipment in building electrical systems is to be connected ("bonded") together and ultimately bonded (grounded) to an earth Building Ground connection at the electrical Service Entrance. This requirement is addressed by the building Equipment Grounding system.
Equipment Grounding (EG) systems incorporate combinations of conduits, raceways, and dedicated Equipment Ground conductors associated with the Hot and Neutral conductors of branch circuits. Connections to EG systems are made via the U-Ground contacts (often referred to as the Green Wire) in electrical outlets. By merely being plugged-in, installations of electronic equipment (computers, sound systems, etc.) are automatically grounded and thus made as safe as possible for operation by nontechnical personnel.
NORMAL EQUIPMENT INTERCONNECTIONS CREATE GROUND LOOPS
Interconnections between groups of grounded electronic equipment via network cables (which incorporate dedicated signal and shield ground conductors) are commonplace. Inductive coupling of powerline surge energy into the Ground Loops formed by these multiple ground connections is inevitable, as current will flow in any conductive path (loop) exposed to the magnetic fields associated with nearby power conductors and electrical equipment. The consequences often appear as noise in sound systems, and mysterious computer network problems ranging from data corruption all the way to catastrophic failure of interface devices, and will be especially evident in installations involving equipment with Pin-1 Problems [1].
It is often suggested that "surge suppressors (devices which limit the magnitude of surge energy) might address these problems. Power Outlet Bars with internal Shunt Mode circuitry are obtained and installed in various equipment locations throughout the building. While perhaps surprising, it is not unusual to find that the net results from these efforts often range from no difference at all throughvague improvements to outright worsening of the original problem(s). In some cases the improvements first realized will unpredictably disappear after some time for no apparent reason.
SHUNT MODE SURGE SUPPRESSORS
Shunt Mode surge suppressors operate by redirecting (shunting) incoming surge energy onto their associated EG conductors, with the result that the local ground reference potential rises due to the current flow through the impedance of the circuit path back to Building Ground. For a ground path length of more than a few feet, this impedance can be substantial, resulting in significant voltages with respect to other "grounded" areas in the building. Any and all equipment connected to a Shunt Mode surge protection device will thus experience an abrupt elevation of its local EG reference potential during surge events. For non-networked standalone applications this may be an academic issue. The additional drawbacks described below are considerably more serious, however.
|